Free sample US customary units
A centrifugal pump circulates a glycol-water coolant (specific gravity 1.08) at 350 gpm through the chiller loop of a plastics molding shop. Gauges on the pump suction and discharge, shown in the figure, are at the same elevation on pipes of equal diameter, and the discharge gauge reads 40 psi higher than the suction gauge. The pump efficiency is 72%. The brake power the pump requires (hp) is most nearly:
Swipe the diagram sideways to see all of it.
- A5.88
- B8.17
- C11.3
- D12.3
Work it out first. On the exam you would have about three minutes.
Show the answer and worked solutionHide the answer and worked solution
AnswerC11.3
Find it in the Handbook
Fluid Mechanics
Centrifugal Pump Characteristics
Fluid power and pump (brake) power
Search (Ctrl+F)
Given
- Flow gpm of coolant, specific gravity
- Gauge difference psi, gauges at the same elevation on equal pipes
- Pump efficiency
Find
Brake (shaft) power the pump needs, in hp
Head added by the pump
With equal elevations and velocities, the head rise is all pressure: lbf/ft³ and ft.
Fluid power
cfs, so hp.
Brake power
hp, closest to 11.3 hp.
Why the other choices are wrong
- A5.88 hp comes from multiplying by the efficiency, hp. That is less than the power the liquid receives, which is impossible: the shaft must supply more, so divide, hp.
- B8.17 hp is the fluid power, , the power that actually reaches the coolant. The question asks for the brake power at the shaft, which also covers the pump's internal losses: divide by to get 11.3 hp.
- D12.3 hp comes from converting the 40 psi to head with water's specific weight ( ft) but then using the coolant's specific weight in the power equation: hp, and hp. Use the same lbf/ft³ in both places (or simply use ), which gives 11.3 hp.
Exam-day tip
When a pump problem gives a pressure rise instead of a head, is just , so the fluid power is and the specific gravity drops out. If you convert the pressure to head, use the same in the power equation.